Symmetricom TimeProvider 1000 User Manual page 161

Edge clock
Hide thumbs Also See for TimeProvider 1000:
Table of Contents

Advertisement

Table 6-5. Event Codes (Continued)
Event ID
Description
CLKLOCK
The local oscillator in
the specified IOC is
in Lock mode
SCAVAIL
The specified IOC is
in SmartClock mode
CRCENA
Indicates whether the
E1 (CAS) inputs are
using CRC4
checking. If the E1
input is provisioned to
read SSMs, then this
value is Enabled
FRMTYPE
Indicates the type of
input framing or the
input frequency. Sets
the output framing
type
OUTSTATE
The specified output
state has changed
RQLEVEL
The received quality
level on the specified
input has changed
097-58001-02 Revision C – August 2005
Keyword
AID
TYPE
EQPT
EQPT
IOC Input Events
T1
T1
T1
T1
Chapter 6 Maintaining and Troubleshooting the TimeProvider
Troubleshooting the TimeProvider
Default Value/
Description of Values
Keyword
n/a
n/a
OFF
OFF – SmartClock is not
available
ON – SmartClock is
available
DISABLE
ENABLE | DISABLE
Output = 2M
1.544M – 1.544 MHz
2M – 2048 kHz
6.312M – 6.312 MHz
CCS – CCS Input
ESF – Extended
SuperFrame input
CC – Composite Clock
input
ISOLATED_1 – Generates
an isolated one test pattern
for T1 outputs
JCC – Japan Composite
Clock
JCC4 – Japan Composite
Clock with 400 Hz
DISABLE
ENABLE – The output
generates the defined
signal type
DISABLE – Disables the
output and clears all active
alarms associated with the
input
n/a
Displays the prior quality
level followed by the new
quality level
TimeProvider User's Guide 161

Advertisement

Table of Contents
loading

This manual is also suitable for:

Timeprovider 1100

Table of Contents