Symmetricom TimeProvider 1000 User Manual page 107

Edge clock
Hide thumbs Also See for TimeProvider 1000:
Table of Contents

Advertisement

Sample Command
ED-SYNC::INP1:TS1000::SSMENA=ENABLE;
Autonomous Message
A 1186 REPT EVT
OF SSM HAS CHANGED,ENABLE\""
;
Defining the SSM Bit Position
After you enable an E1 (CCS) input to read SSMs, you must then define the bit
containing the SSM.
ED-SYNC:[<tid>]:<aid>:[<ctag>]::<keyword>=<value>;
This command has a default access level of ADMIN.
<aid>
<keyword>
INPp
p = 1 | 2
SSMBIT
Sample Command
ED-SYNC::INP1:TS1000::SSMBIT=4;
This command sets the SSM bit to position 4 in the E1 input string on Input 1.
Autonomous Message
A 1187 REPT EVT
CHANGED,4\""
;
097-58001-02 Revision C – August 2005
TP-SSU 03-10-24 11:02:28
"INP1,T1:NA,SSMENA,NSA,03-10-24 11-02-28:\"INPUT READING
<value>
4 | 5 | 6 | 7 | 8
TP-SSU 03-10-24 11:05:18
"INP1,T1:NA,SSMBIT,NSA,03-10-24 11-05-18:\"E1 SSM BIT HAS
Chapter 4 Provisioning the TimeProvider
Provisioning the Input Reference
Description
System inputs
Provisions the E1
(CCS) SSM bit position.
TimeProvider User's Guide 107
Default value
8