MX5, MX10, MX40, and MX80 3D Universal Edge Router Hardware Guide
Grounding Cable Specifications
Related
Documentation
MX5, MX10, MX40, and MX80 Site Preparation Checklist
Table 20: MX80 Site Preparation Checklist
Item or Task
Environment
Verify that environmental factors such as
temperature and humidity do not exceed router
tolerances.
Power
Locate sites for connection of system
grounding.
44
Figure 25: Grounding Cable Lug
1.69
End view
0.2
0.38
dia.
0.06
0.625
CAUTION:
Before router installation begins, a licensed electrician must attach
a cable lug to the grounding and power cables that you supply. A cable with
an incorrectly attached lug can damage the router.
You must provide one grounding cable that meets the following specifications: 6-AWG
2
(13.3 mm
), minimum 60° C wire, or as required by the local code.
Tools and Parts Required for MX5, MX10, MX40, and MX80 Router Grounding and
Power Connections on page 87
Preventing Electrostatic Discharge Damage to an MX5, MX10, MX40, and MX80 Router
on page 194
MX5, MX10, MX40, and MX80 Routers AC Power Specifications on page 53
MX5, MX10, MX40, and MX80 Routers DC Power Specifications on page 59
The checklist in
Table 20 on page 44
preparing a site for router installation.
For More Information
"MX5, MX10, MX40, and MX80 Router
Environmental Specifications" on
page 42
"MX5, MX10, MX40, and MX80 Router
Grounding Specifications" on page 43
6 AWG conductor
All measurements in inches
summarizes the tasks you must perform when
Performed By
Copyright © 2017, Juniper Networks, Inc.
Date