Table 18: ACX7100-32C Router Environmental Tolerances
Description
Altitude
Relative humidity
Temperature
Seismic
NOTE: Install ACX Series devices only in restricted-access areas, such as dedicated equipment
rooms and equipment closets, in accordance with Articles 110-16, 110-17, and 110-18 of the
National Electrical Code, ANSI/NFPA 70.

Grounding Cable and Lug Specifications for ACX7100-32C

For installations that require a separate grounding conductor to the chassis, you must ground the router
properly before you connect power to ensure proper operation and to meet safety and electromagnetic
interference (EMI) requirements. To ground an ACX7100-32C router, connect a grounding cable to earth
ground, and then attach the grounding cable to the chassis grounding points.
Tolerance
No performance degradation up to 6,000 feet (1,829 meters)
Normal operation ensured in relative humidity range of 5% through
90%, non-condensing.
Short-term operation ensured in relative humidity range of 5%
through 93%, non-condensing.
NOTE: As defined in NEBS GR-63-CORE, short-term events can be
up to 96 hours in duration but not more than 15 days per year.
Normal operation ensured in temperature range of 32° F through
104° F (0° C through 40° C).
Non-operating storage temperature in shipping container: –40° F
through 158° F (–40° C through 70° C).
Complies with Zone 4 earthquake requirements according to NEBS
GR-63-CORE.
36