List Of Input/Output Signal Details - Mitsubishi QD75P1N User Manual

Q series
Table of Contents

Advertisement

3 SPECIFICATIONS AND FUNCTIONS

3.4.3 List of input/output signal details

Signal name
Manual pulse generator A
phase (PULSER A+)
Manual pulse generator B
phase (PULSER B+)
Manual pulse generator A
common (PULSER A-)
Manual pulse generator B
common (PULSER B-)
Zero signal (+24V)
(PG024)
Zero signal (+5V)
(PG05)
Zero signal common
(PG0COM)
Pulse output F (+)
(PULSE F+)
Pulse output F (–)
(PULSE F-)
Pulse output R (+)
(PULSE R+)
Pulse output R (–)
(PULSE R-)
Pulse output F
(PULSE F)
Pulse output F common
(PULSE COM)
Pulse output R
(PULSE R)
Pulse output R common
(PULSE COM)
Upper limit signal (FLS)
Lower limit signal (RLS)
The details of each QD75 external device connection connector are shown below:
Pin No.
AX1 AX2 AX3 AX4
1A19
1A20
1B19
1B20
1A8
1B8
2A8
2B8
1A9
1B9
2A9
2B9
1A10 1B10 2A10 2B10 • Common for zero signal (+5V) and zero signal (+24V).
1A15
1B15
2A15
2B15
1A16
1B16
2A16
2B16
1A17
1B17
2A17
2B17
1A18
1B18
2A18
2B18
1A15
1B15
2A15
2B15
1A16
1B16
2A16
2B16
1A17
1B17
2A17
2B17
1A18
1B18
2A18
2B18
1A1
1B1
2A1
2B1
1A2
1B2
2A2
2B2
(Negative logic is selected by external I/O signal logic selection)
• Input the pulse signal from the manual pulse generator A phase and B
phase.
• If the A phase leads the B phase, the positioning address will increase at the
rising and falling edges of each phase.
• If the B phase leads the A phase, the positioning address will decrease at the
rising and falling edges of each phase.
[When increased]
A phase
B phase
Positioning
+1+1+1+1+1+1+1+1
address
• Input the zero signal for machine OPR.
Use the pulse encoder's zero signal and so on.
• Also use this signal when the machine OPR method is the stopper method
and the OPR complete is input from an external source.
• The zero signal is detected at turning from OFF to ON.
• Output the positioning pulses and pulse sign for the differential driver output
system compatible drive unit.
(QD75D
N/QD75D
only)
• Output the positioning pulses and pulse sign for the open collector output
system compatible drive unit.
(QD75P
N/QD75P
only)
• This signal is input from the limit switch installed at the upper limit position of
the stroke.
• Positioning will stop when this signal turns OFF.
• When OPR retry function is valid, this will be the upper limit for finding the
near-point dog signal.
• This signal is input from the limit switch installed at the lower limit position of
the stroke.
• Positioning will stop when this signal turns OFF.
• When OPR retry function is valid, this will be the lower limit for finding the
near-point dog signal.
3 - 24
MELSEC-Q
Signal details
[When decreased]
A phase
B phase
Positioning
-1 -1 -1 -1 -1 -1 -1 -1
address