11 MANUAL CONTROL
Forward run JOG start signal
[Y8, YA, YC, YE]
Reverse run JOG start signal
[Y9, YB, YD, YF]
BUSY signal [XC, XD, XE, XF]
Md. 26
Axis operation status
Pulse output to an
external source (PULSE)
Positioning operation
Positioning complete signal
[X14, X15, X16, X17]
Model
QD75P N/QD75D N
QD75P /QD75D
JOG operation timing and processing time
The following drawing shows details of the JOG operation timing and processing
time.
ON
OFF
OFF
ON
OFF
t1
Standby
t3
OFF
Fig. 11.5 JOG operation timing and processing times
Normal timing times
1.0 to 3.0ms
1.0 to 3.0ms
Delays may occur in the t1 timing time due to the operation status of other axes.
t2
t4
JOG operation
Standby
t1
t2
0 to 0.9ms
0 to 1.8ms
11 - 6
MELSEC-Q
t3
1.3 to 2.2ms
0 to 0.9ms
2.7 to 4.4ms
0 to 1.8ms
t4