Mitsubishi QD75P1N User Manual page 334

Q series
Table of Contents

Advertisement

9 MAJOR POSITIONING CONTROL
Restrictions
A 0.9ms (QD75P N /QD75D N) or 1.8ms (QD75P /QD75D ) error will occur in
the current value update timing when the stored "current feed value" is used in the
control.
A 0.9ms (QD75P N /QD75D N) or 56.8ms (QD75P /QD75D ) error will occur
in the current value update timing when the stored "machine feed value" is used in
the control.
Monitoring the current value
The "current feed value" and "machine feed value" are stored in the following
buffer memory addresses, and can be read using a "DFRO (P) instruction" or
"DMOV (P) instruction" from the CPU module.
Md.20 Current feed value
Md.21 Machine feed value
(1) The following shows the examples of programs to read out the current feed
value of the axis 1 to D104 and D105 when X40 is turned ON.
(a) For the DFRO(P) instruction
(b) For the DMOV(P) instruction
Buffer memory addresses
Axis 1
Axis 2
800, 801
900, 901
802, 803
902, 903
9 - 18
MELSEC-Q
Axis 3
Axis 4
1000, 1001
1100, 1101
1002, 1003
1102, 1103