6.1.5 External Teach-in (via PLC inputs)

This function is required only for special applications and is not available as default. If required, it can be
activated according to chapter "7. Start-up".
Note: During Teach-In one sheet of nominal thickness must be placed in front of the
sensor.
Attention: A zero adjust procedure has to be executed immediately before the
Teach-in procedure.
OUT 0
IN 0,1,3-8
IN 2
OUT 3
OUT 2
OUT 1
Check whether the output OUT0 „Enable" has switched to HIGH (ready for operation),
1
otherwise there is a fault condition.
Before initiating the Teach-In, all inputs must be LOW for 30 milliseconds. One sheet of nominal thickness
2
must be placed in front of the sensor.
Switch the input IN2 „Teach-In" to HIGH.
3
Within 30 milliseconds the outputs OUT1-3 have switched to LOW.
4
After point 4 or 30 milliseconds after point 3 switch the input IN2 „Teach-In" to LOW.
5
Now the unit performs a „Teach-In" procedure, which is completed within 7s. Then the outputs OUT1-3
6
switch to HIGH.
Example:
Check whether the output OUT0 „Enable" has switched to HIGH.
1
One sheet must be in front of the sensor. All inputs must be LOW for more than 30 milliseconds.
2
Switch input IN2 to HIGH. 4 After 30 milliseconds check whether outputs 1-3 have switched to LOW.
3
Switch input IN2 „Teach-In" to LOW.
5
After >7 seconds check whether the outputs OUT1-3 have switched to HIGH.
6
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · D-75210 Keltern · Telefon (0049) (07236) 9392-0 · Telefax (0049) (07236) 9392-33
OPERATING INSTRUCTIONS
DOUBLE SHEET DETECTOR R1000 UDK20
Enable
Teach-In
0-Sheet
1-Sheet
2-Sheet
1
min.
max.
30ms
30ms
2
3
4
min.
30ms
5
max. 7 sec.