Faults concerning keyboard

No.
Cause
55
Changing of system / program parameters is not
possible, for a serial fieldbus function is active (e.g.
Teach-In or Measurement start).
56
Changing of system / program parameters is not
possible, for a parallel function is active (e.g. Teach-
In or Measurement start).
57
Changing of system / program parameters is not
possible, since the parameter channel is opened via
Field bus.
9.8

Faults concerning supply voltage

No.
Cause
60
Operating voltage was below 20 VDC.
62
Sensor voltage too low.
9.9

Faults Sensor Switch Box

No.
Cause
65
Error in the Sensor Switch Box.
9.10

Faults concerning PLC parallel inputs

No.
Cause
71
The parallel function is not possible, because the
system was configured for the "demo mode".
72
The parallel function is not possible, because the
system is operated via the keyboard.
73
The parallel function cannot be performed because a
fieldbus function is active, e.g. "Teach-In" via the
fieldbus and "measurement start" via parallel inputs.
74
The parallel function cannot be performed because
the parameter channel is opened via Field bus.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Double Sheet Detector R1000 series UDK20
with integrated fieldbus interface
Manual
Fault messages, causes and remedies
Remedy
Await completion of fieldbus function or terminate it.
Await completion of fieldbus function or terminate it.
Close the parameter channel.
Remedy
Check power supply.
Check external power supply
(insufficient power ?).
Contact Roland Electronic Service Department.
Remedy
If a Sensor Switch Box is connected, check box and
cables.
Otherwise read the notes in chapter 9.1.
Remedy
Configure the system parameter "Measurement mode"to
"external continuous measurement" or "single
measurement".
Terminate the operation via keyboard and return the
system to neutral operation by pressing the menu key.
Wait for the completion of the fieldbus function or
terminate it and repeat parallel function.
Close the parameter channel.