3 SPECIFICATIONS
3.4.3 CH.

averaging time/count (buffer memory addresses 1 to 4: Un\G1 to 4)

3.4.4 Averaging processing designation (buffer memory address 9: Un\G9)

Example
To specify count averaging for channels 1, 5, time averaging for channels 2, 7, and sampling processing for
other channels, store 5342H (21314) into the buffer memory address 9 (Un\G9).
b15 b14 b13 b12 b11 b10
0
1
CH.8 CH.7 CH.6 CH.5 CH.4 CH.3 CH.2 CH.1
5
3 - 14
(1) Set the averaging time or averaging count for each channel specified for
averaging processing (buffer memory address 9: Un\G9).
(2) Setting can be made within the following ranges.
Time-specified averaging processing: 160 to 5000ms
Count-specified averaging processing: 4 to 62500 times
If you set any value outside the range, it will result in an error and operation will be
performed with the old setting.
(3) This setting will be invalid if sampling is specified for averaging processing
designation (buffer memory address 9: Un\G9).
(4) At power-on or reset, the CH.
time 0/averaging count 0).
(5) The Operation Condition Setting Request (Y9) must be turned on/off to make this
setting valid.
(6) Refer to Section 3.4.4 for details of sampling/time averaging processing/count
averaging processing.
(1) To select sampling or averaging processing, write values to the buffer memory
address 9 (Un\G9).
(2) When you selected averaging processing, choose time averaging or count
averaging.
(3) This setting defaults to all-channel sampling processing.
(4) For the Q64RD, b4 to b7 and b12 to b15 (CH.5 to CH.8) are invalid.
b15 b14 b13 b12 b11 b10
CH.8 CH.7 CH.6 CH.5 CH.4 CH.3 CH.2 CH.1
Designation of averaging-processed channels
1: Averaging processing
0: Sampling processing
(5) The Operation Condition Setting Request (Y9) must be turned on/off to make this
setting valid.
b9
0
1
0
0
1
3
averaging time/count is set to 0000
b9
b8
CH.8 CH.7 CH.6 CH.5 CH.4 CH.3 CH.2 CH.1
b8
b7
b6
b5
b4
1
0
1
0
0
CH.8 CH.7 CH.6 CH.5 CH.4 CH.3 CH.2 CH.1
4
b7
b6
b5
b4
b3
Designation of time/count
1: Time averaging
0: Count averaging
b3
b2
b1
b0
0
0
1
0
5342
2
MELSEC-Q
(averaging
H
b2
b1
b0
(21314)