Setting Of Input Data Status From Data Link Faulty Station - Mitsubishi FX2N-16CCL-M User Manual

Cc-link master module
Hide thumbs Also See for FX2N-16CCL-M:
Table of Contents

Advertisement

FX2N-16CCL-M CC-Link System Master Block
5.8

Setting of Input Data Status from Data Link Faulty Station

The status of the data input (received) from a data link faulty station can be set.
1) Target input (received) data
The figure below shows the buffer memory area regarded as the setting target.
Master station
Remote input (RX)
Station No. 1
Station No. 2
Station No. 3
Station No. 4
Remote output (RY)
Station No. 1
Station No. 2
Station No. 3
Station No. 4
Remote register (RWw)
Station No. 1
Station No. 2
Station No. 3
Station No. 4
Remote register (RWr)
Station No. 1
Station No. 2
Station No. 3
Station No. 4
2) Setting method
Set the status using the condition setting DIP switch SW4 in the master block.
OFF: Clear (setting at shipment)
ON : Keeps the status right before error
When a data link faulty station is set as error invalid station, the data (remote input
RX and remote output RY) input from the station is kept without regard to the setting
of the SW4.
Remote I/O station
(station No. 1)
Input
Output
Point
Remote device station
(station No. 2)
Remote input (RX)
Remote output (RY)
Remote register
(RWw)
Remote register
(RWr)
: Target area of clear/keep
: Area kept without regard to the setting
Functions 5
5-17