Setting the DIP switches

Power down the NX-507E/NX-508E output expander.
1.
Set the DIP switches according to Table 10. NX-507E/NX-508E output expander DIP
2.
switches.
Note:
Switches 1-3 set the module address. DIP switch 4 enables the tamper.
•If DIP switch 4 is ON, the NX-507E/NX-508E generates a tamper alarm when
the TAM line is unconnected to the COM line.
•If DIP switch 4 is OFF, the NX-507E/NX-508E does not generate a tamper
alarm if the TAM line is unconnected to the COM line.
Table 10. NX-507E/NX-508E output expander DIP switches
DIP switch 1-3 settings
= ON
= OFF
The outputs can be logged in the event log. The output numbers that appear in the event
3.
log are linked to a selected NX-507E/NX-508E output expander address.
Power up the NX-507E/NX-508E output expander. The position of all switches is
4.
updated when the NX-507E/NX-508E output expander is powered up.
Flashes during normal operation.
Factory use only.
Address
Outputs
24
1-7
25
9-15
26
17-23
27
25-31
DIP switch 1-3 settings
Address
Outputs
28
33-39
29
41-46
30
49-55
31
57-63