The UPS ventilation requirements are shown in Table 3‐3.
Table 3‐3. Air Conditioning or Ventilation Requirements During Full Load Operation
Rating
450 kVA
500 kVA
550 kVA
t
Power Xpert
9395 UPS (450–550 kVA) Installation and Operation Manual
Input/Output
Heat Rejection
BTU/hr  1000/ (kg-cal/hr)
Voltage
400/400
87 (21886)
480/480
88 (22107)
400/400
96 (24318)
480/480
97 (24563)
400/400
106 (26479)
480/480
107 (27020)
Figure 3‐1. UPS Cabinet Dimensions (Front View)
S
164201701 Rev 3 www.eaton.com/powerquality
UPS INSTALLATION PLAN AND UNPACKING
Ventilation Required for
Cooling Air Exhaust
Approximately 1652 liter/sec (3500 CFM)
With Field Installed UPM
Approximately 2478 liter/sec (5250 CFM)
Dimensions are in millimeters [inches].
3-3