80070114-2201ffff
Sensor [SensorElementName] has transitioned from normal to non-critical state. (TPM Phy
Pres Set)
Explanation: This message is for the use case when an implementation has detected a Sensor transitioned to
non-critical from normal.
May also be shown as 800701142201ffff or 0x800701142201ffff
Severity: Warning
Alert Category: Warning - Other
Serviceable: Yes
1.
Complete the administrative tasks that require the TPM physical presence switch to be in the ON position.
2.
Restore the physical presence switch to the OFF position.
3.
Reboot the system.
4.
(Trained technician only) If the error continues, replace the planar.
80070128-2e01ffff
Sensor [SensorElementName] has transitioned from normal to non-critical state. (ME Recovery)
Explanation: This message is for the use case when an implementation has detected a Sensor transitioned to
non-critical from normal.
May also be shown as 800701282e01ffff or 0x800701282e01ffff
Severity: Warning
Alert Category: Warning - Other
Automatically notify Support: No
User response: None
80070201-0301ffff
Sensor [SensorElementName] has transitioned to critical from a less severe state. (CPU 1
OverTemp)
Explanation: This message is for the use case when an implementation has detected a Sensor transitioned to critical
from less severe.
May also be shown as 800702010301ffff or 0x800702010301ffff
Alert Category: Critical - Temperature
SNMP Trap ID: 0
80070114-2201ffff • 80070201-0301ffff
Appendix A. Integrated management module II (IMM2) error messages