IBM pSeries 690 Service Manual page 549

Hide thumbs Also See for pSeries 690:
Table of Contents

Advertisement

Error Code Description
4067 0006 Bus tests detected fault in MCM module 3
4067 0007 Bus tests detected fault in L3 VPD card
4067 000A Bus tests detected fault in primary I/O book 1
(slot 0)
4067 000B Bus tests detected fault in secondary I/O book
(slot 1)
4067 000C Bus tests detected fault in I/O book 3 (slot 2)
4067 000D Bus tests detected fault in I/O book 4 (slot 3)
4067 000E CUoD capacity card
4067 0010 Bus tests detected fault in Memory book (slot 0) Memory book (slot 0)
4067 0011 Bus tests detected fault in Memory book (slot 1) Memory book (slot 1)
4067 0012 Bus tests detected fault in Memory book (slot 2) Memory book (slot 2)
4067 0013 Bus tests detected fault in Memory book (slot 3) Memory book (slot 3)
4067 0014 Bus tests detected fault in Memory book (slot 4) Memory book (slot 4)
4067 0015 Bus tests detected fault in Memory book (slot 5) Memory book (slot 5)
4067 0016 Bus tests detected fault in Memory book (slot 6) Memory book (slot 6)
4067 0017 Bus tests detected fault in Memory book (slot 7) Memory book (slot 7)
4067 00B0 Bus tests detected possible problem with bus
controller or CSP code
4067 00B1 Bus tests detected possible problem with bus
controller
Action/
Possible Failing FRU
MCM module 3 and VPD card
Location: U1.18-P1-C2 and U1.18-P1-H2.6
1. L3 VPD card
Location: U1.18-P1-H2.1
(Order the L3 cache module FRU to obtain
a new L3 VPD card. Return the L3 cache
module that was included in the FRU kit,
and the failing L3 VPD card as "new
defective".)
2. Primary I/O book
Location: U1.18-P1-H2
Go to "MAP 1540: Problem Isolation
Procedures" on page 298.
Go to "MAP 1540: Problem Isolation
Procedures" on page 298.
Go to "MAP 1540: Problem Isolation
Procedures" on page 298.
Go to "MAP 1540: Problem Isolation
Procedures" on page 298.
1. Replace the CUoD capacity card
Location: U1.18-P1-H2.2
2. Ask the customer to reenter the CUoD
activation keys.
Location: U1.18-P1-M2
Location: U1.18-P1-M3
Location: U1.18-P1-M7
Location: U1.18-P1-M6
Location: U1.18-P1-M4
Location: U1.18-P1-M8
Location: U1.18-P1-M5
Location: U1.18-P1-M1
1. Check for system firmware updates.
2. Primary I/O book,
Location: U1.18-P1-H2
3. Call service support.
1. Check for system firmware updates.
2. Primary I/O book,
Location: U1.18-P1-H2
3. Call service support.
Chapter 5. Error Code to FRU Index
529