Table 3–8
EMU Fault Code Displays (Continued)
Fault Code, Cause, Corrective
Action
Fault Code 07
Invalid configuration.
Requires an array controller-specific
action (see the array controller
documentation).
Fault Code 08
Two PVA SCSI ID switch settings are
the same.
1.
Ensure the PVA SCSI ID switch settings are as follows:
Master enclosure — 0
First expansion enclosure — 2
Second expansion enclosure — 3
2.
If any PVA SCSI ID switch setting is changed, the controllers must be RESET to recognize the
new setting.
3.
Replace each of the PVAs in sequence (first the master, then the expansions) until the fault
condition clears.
Fault Code 09
An EMU is installed in a PVA slot.
Remove the EMU from the PVA slot and
install it into the slot immediately to the
left.
Environmental Monitoring Unit
EMU LED Display
8
4
8
4
8
4
UltraSCSI RAID Enclosure 3–25
7
6
5
3
2
1
CXO5766A
7
6
5
3
2
1
CXO5767A
7
6
5
3
2
1
CXO5768A