Table 3–8
EMU Fault Code Displays (Continued)
Fault Code, Cause, Corrective
Action
Fault Code 02
Both microcode images are bad.
1.
Load microcode image into the
EMU from a PC.
2.
Replace the EMU.
Fault Code 03
Either a PVA SCSI ID switch setting is
invalid (set to 1, 4, 5, 6, or 7) or there is
no master enclosure identified (SCSI
bus ID = 0).
1.
Ensure PVA SCSI ID switches settings are as follows:
Master enclosure — 0
First expansion enclosure — 2
Second expansion enclosure — 3
2.
If any PVA SCSI ID switch setting is changed, the controllers must be RESET to recognize the
new setting.
3.
Replace each of the PVAs in sequence (first the master, then the expansions) until the fault
condition clears.
Environmental Monitoring Unit
EMU LED Display
8
4
8
4
UltraSCSI RAID Enclosure 3–23