Parameter
Function name
No.
b040
Torque limit selection
Torque limit 1
(Four-quadrant mode
b041
forward power
running)
Torque limit 2
(Four-quadrant mode
b042
reverse
regeneration)
Torque limit 3
(Four-quadrant mode
b043
reverse power
running)
Torque limit 4
(Four-quadrant mode
b044
forward
regeneration)
Torque LADSTOP
b045
selection
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
Monitor or data range
00: Four-quadrant separate setting
01: Terminal switch
02: Analog input
03: Option 1
04: Option 2
0. to 200. (0.4 to 55 kW)
0. to 180. (75 to 132 kW)
no (Torque limit disabled)
0. to 200. (0.4 to 55 kW)
0. to 180. (75 to 132 kW)
no (Torque limit disabled)
0. to 200. (0.4 to 55 kW)
0. to 180. (75 to 132 kW)
no (Torque limit disabled)
0. to 200. (0.4 to 55 kW)
0. to 180. (75 to 132 kW)
no (Torque limit disabled)
00: Disabled
01: Enabled
3-7 Parameter List
Changes during
Default
operation
Unit
setting
Normal b031 = 10
00
No
Yes
-⎯
150.
No
Yes
%
150.
No
Yes
%
150.
No
Yes
%
150.
No
Yes
%
00
No
Yes
Page
4-57
4-59
3
4-57
4-59
4-57
4-59
4-59
3-34