Omron SYSDRIVE RX Series User Manual page 124

High-function general-purpose inverter
Table of Contents

Advertisement

4-2 Function Mode
(Example 1) A015/A105: 00
Max.
frequency
A012/A102
A011/A101
4
0
A013/A103
(0 V/0 mA)
Adjusting the FE-FC Terminal
Parameter No.
A111
A112
A113
A114
Related functions
* Below is the ratio from -10 to 10 V.
-10 to 0 V: -100% to 0%
0 to 10 V: 0% to 100%
• For example, to input voltage ranging from -5 to 5 V on the
FE-FC terminal, set A113 to -50%, and A114 to 50%.
4-15
A014/A104
100%
Analog input
(10 V/20 mA)
Function name
-400. to 400.
FE start frequency
(Set a start frequency.)
-400. to 400.
FE end frequency
(Set an end frequency.)
-100. to 100.:
FE start ratio
(Set a start ratio relative to an external
frequency reference of -10 to 10 V.
-100. to 100.:
FE end ratio
(Set an end ratio relative to an external
frequency reference of -10 to 10 V.
(Example 2) A015/A105: 01
Max.
frequency
A012/A102
A011/A101
0
A013/A103
(0/OI)
(0 V/0 mA)
Data
A003, A203, A303, A081, A082
(Example 3)
Forward
max. frequency
(-10 V)
-100% A113
A014/A104
100%
Analog input
(10 V/20 mA)
(0/OI)
Default
Unit
setting
0.00
Hz
0.00
-100.
*
)
%
100.
*
)
A112
Analog input
A114 100%
(+10 V)
A111
Reverse
max. frequency
(02)