Omron SYSDRIVE RX Series User Manual page 197

High-function general-purpose inverter
Table of Contents

Advertisement

Parameter No.
Function name
H073
Gain switching time
•If control gain switching is selected in the multi-function input selection, turning off the signal
selects the gain setting of H050, H250, H051, H251, H052, or H252. Turning on the signal selects
the gain setting of H070, H071, or H072.
•If control gain switching is not selected in multi-function inputs 1 to 8 (C001 to C008), the gain
setting conforms to the status in which the signal is turned off.
UP/DOWN Function
•This function allows you to change the Inverter output frequency using the UP and DWN terminals
of the multi-function inputs.
Data
Symbol
27
UP
28
DWN
29
UDC
Available input terminals
Note: Do not turn on/off the UP/DWN terminal after shutting off the power. Otherwise, the Inverter may not store
data correctly.
•Allocate "27" (UP) and "28" (DWN) to any of multi-function inputs 1 to 8 (C001 to C008).
•This function is enabled only when frequency reference selection A001 is set to "01" or "02". If "01"
(terminal) is selected, however, this function is enabled for multi-step speed operation only.
•When you use an external analog input as frequency reference input, or when you set the jogging
operation frequency, this function is disabled.
•While the UP/DWN terminal is turned on, the acceleration/deceleration time depends on F002,
F003/F202, F203/F302, and F303. To switch between the 1st/2nd/3rd controls, allocate 08 (SET)/
17 (SET3) to the desired multi-function input and then turn on/off the SET terminal.
•You can store a frequency set value after UP/DWN adjustment. Choose whether to store the value
with C101.
Also, you can clear the stored frequency set value.
By allocating "29" (UDC) to a multi-function input and turning on/off the UDC terminal, you can
clear or store the frequency reference setting adjusted at UP/DOWN.
Parameter No.
Data
00
C101
01
0. to 9999. (ms):
Taper time during gain switching
Function name
Status
UP/DWN function
accelerated
UP/DWN function
decelerated
UP/DWN function
data clear
Does not store the frequency reference adjusted at UP/DWN.
After restoring the power, returns to the value set before UP/DWN adjustment.
Stores the frequency reference adjusted at UP/DWN.
After restoring the power, maintains the set value after UP/DWN adjustment.
Data
Description
Increases the current speed during the signal
ON
input period.
OFF
Keeps the current speed.
Decreases the current speed during the signal
ON
input period.
OFF
Keeps the current speed.
ON
Clears the stored UP/DWN speed.
OFF
Keeps the stored UP/DWN speed.
C001 to C008
Description
4-2 Function Mode
Default setting
Unit
100.
ms
4-88
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents