Omron SYSDRIVE RX Series User Manual page 211

High-function general-purpose inverter
Table of Contents

Advertisement

Starting Contact Signal
•While the Inverter is receiving the RUN command, a starting contact signal is output.
•The output is enabled regardless of the setting of RUN command source selection A002.
•If inputs FW and RV are simultaneously turned on, the Inverter stops.
Parameter No.
Function name
Multi-function output
C021 to C025
terminal selection
Relay output (MA, MB)
C026
function selection
Forward command
Reverse command
Starting contact signal (FR)
Fin Overheat Warning
•This function monitors the Inverter's internal fin temperature and outputs a signal when the
temperature exceeds the fin overheat warning level (C064).
Parameter No.
Function name
Multi-function output
C021 to C025
terminal selection
Relay output (MA, MB)
C026
function selection
Fin overheat warning
C064
41: FR (starting contact signal)
42: OHF (cooling fin overheat warning)
0. to 200.: Set a temperature to output the
level
overheat warning signal.
4-2 Function Mode
Data
Default setting
Data
Default setting
Unit
05
Unit
05
°C
120
4-102
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents