Omron SYSDRIVE RX Series User Manual page 258

High-function general-purpose inverter
Table of Contents

Advertisement

4-4 Communication Function
<Command 04>
Reads the Inverter status.
•Transmission frame
Frame format
Station No.
Command
4
•Response frame
Frame format
Station No.
*
Inverter status data includes the following three elements (A, B, and C).
Data
4-149
STX
Station No.
Command
Description
STX
Control code (Start of TeXt)
Station No. of the target Inverter
Transmission command
BCC
Block check code
CR
Control code (Carriage Return)
STX
Station No.
Description
STX
Control code (Start of TeXt)
Station No. of the target Inverter
Data
Data
BCC
Block check code
CR
Control code (Carriage Return)
Status A
Status B
BCC
Data size
1 byte
2 bytes
2 bytes
2 bytes
1 byte
Data
BCC
Data size
1 byte
2 bytes
8 bytes
2 bytes
1 byte
Status C
00 (Reserved)
CR
Setting
STX (0x02)
01 to 32
04
Exclusive OR from station No. to
data. (Refer to page 4-157.)
CR (0x0D)
CR
Setting
STX (0x02)
01 to 32
*
Exclusive OR from station No. to
data. (Refer to page 4-157.)
CR (0x0D)