Omron SYSDRIVE RX Series User Manual page 40

High-function general-purpose inverter
Table of Contents

Advertisement

2-2 Wiring
2
R/L1
S/L2
+1-P/+2
G
short-circuit bar
When not using the DC
reactor, keep the +1-P/+2
short-circuit bar attached.
[EMC filter function switching method]
EMC filter enabled
R/L1
S/L2
G
+1-P/+2
short-circuit bar
When not using the DC
reactor, keep the +1-P/+2
short-circuit bar attached.
[EMC filter function switching method]
EMC filter enabled
2-17
Terminal arrangement
CHARGE LED indicator
T/L3
+1
P/+2
N/-
Ground terminal with
short-circuit bar (shaded area)
for EMC filter function switching
EMC filter disabled (factory default)
CHARGE LED indicator
T/L3
+1
P/+2
EMC filter disabled (factory default)
Ro
To
U/T1
V/T2
W/T3
G
Ro To
N/-
U/T1
V/T2
W/T3
G
Ground terminal with
short-circuit bar
(shaded area) for EMC
filter function switching
Applicable model
G
3G3RX-A2450
3G3RX-A4450
3G3RX-A4550
Ro,To: M4
Ground terminal: M8
Others: M8
G
3G3RX-A2550
Ro,To: M4
Ground terminal: M8
Others: M10