Parameter
Function name
No.
Overload limit
b021
selection
b022
Overload limit level
Overload limit
b023
parameter
Overload limit
b024
selection 2
b025
Overload limit level 2
Overload limit
b026
parameter 2
Overcurrent
b027
suppression function
Frequency pull-in
b028
restart level
Frequency pull-in
b029
restart parameter
Starting frequency at
b030
frequency pull-in
restart
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
Monitor or data range
00: Disabled
01: Enabled in acceleration/constant speed
operation
02: Enabled in constant speed operation
03: Enabled in acceleration/constant speed
operation (Accelerates during
regeneration)
0.20 × Rated current to 2.00 × Rated current
(0.4 to 55 kW)
0.20 × Rated current to 1.80 × Rated current
(75 to 132 kW)
0.10 to 30.00
00: Disabled
01: Enabled in acceleration/constant speed
operation
02: Enabled in constant speed operation
03: Enabled in acceleration/constant speed
operation (Accelerates during
regeneration)
0.20 × Rated current to 2.00 × Rated current
(0.4 to 55 kW)
0.20 × Rated current to 1.80 × Rated current
(75 to 132 kW)
0.10 to 30.00
00: Disabled
01: Enabled
0.20 × Rated current to 2.00 × Rated current
(0.4 to 55 kW)
0.20 × Rated current to 1.80 × Rated current
(75 to 132 kW)
0.10 to 30.00
00: Frequency at interruption
01: Max. frequency
02: Set frequency
3-7 Parameter List
Changes during
Default
operation
Unit
setting
Normal b031 = 10
01
No
Yes
1.50
×
Rat-
No
Yes
A
ed
cur-
rent
1.00
No
Yes
s
01
No
Yes
1.50
×
Rat-
No
Yes
A
ed
cur-
rent
1.00
No
Yes
s
01
No
Yes
Rat-
ed
No
Yes
A
cur-
rent
0.50
No
Yes
s
00
No
Yes
Page
3
4-49
4-51
4-43
4-69
3-32