4-4 Communication Function
Register Number List
R/W in the list shows whether the coil or holding register accepts reading and/or writing.
<Coil Number List>
Coil No.
0000h
Not used
0001h
RUN command
0002h
Rotation direction command
4
0003h
External trip (EXT)
0004h
Trip reset (RS)
0005h
Not used
0006h
Not used
0007h
Multi-function input terminal S1
0008h
Multi-function input terminal S2
0009h
Multi-function input terminal S3
000Ah
Multi-function input terminal S4
000Bh
Multi-function input terminal S5
000Ch
Multi-function input terminal S6
000Dh
Multi-function input terminal S7
000Eh
Multi-function input terminal S8
000Fh
Operation status
0010h
Rotation direction
0011h
Inverter ready
0012h
Not used
0013h
RUN (during RUN)
*1. When either the control circuit terminal block or the coil is turned on, these settings are ON.
The control circuit terminal block has the priority for the multi-function input terminals.
If the master cannot reset the coil ON status because of communication disconnection, turn the control
circuit terminal block from ON to OFF to turn off the coil.
*2. The communications error is retained until a fault reset is input. (Can be reset during operation.)
4-169
R: Read only
R/W: Read and write enabled
Item
R/W
Description
1: Run
R/W
0: Stop (Enabled when A002 = 03)
1: Reverse
R/W
0: Forward (Enabled when A002 = 03)
R/W
1: Trip
R/W
1: Reset
1: ON
R/W
*1
0: OFF
1: ON
R/W
*1
0: OFF
1: ON
R/W
*1
0: OFF
1: ON
R/W
*1
0: OFF
1: ON
R/W
*1
0: OFF
1: ON
R/W
*1
0: OFF
1: ON
R/W
*1
0: OFF
1: ON
R/W
*1
0: OFF
1: Run
R
0: Stop (Interlocked with d003)
1: Reverse
R
0: Forward (Interlocked with d003)
1: Ready
R
0: Not ready
1: During trip
R
0: Normal