Omron SYSDRIVE RX Series User Manual page 149

High-function general-purpose inverter
Table of Contents

Advertisement

Pattern Curve Parameter (Curve Factor)
•Determine a curve factor with reference to the figures below.
Output frequency (Hz)
Target
frequency
(100%)
96.9
10 02
82.4
17.6
02
3.1
10
25
50
75
Acceleration time before reaching the
output frequency set value (100%)
•The S pattern has an intermediate section where acceleration/deceleration time is shortened.
•If LAD cancel (LAC) is selected for a multi-function input and that input is turned on, the
acceleration/deceleration pattern is ignored, and the output frequency instantaneously follows the
reference frequency.
EL-S Curve Ratio
If the EL-S pattern is used, you can set a curve ratio (A151 to A153) individually for acceleration and
deceleration.
If all settings are "50 (%)", the Inverter operates in the same manner as with the S curve.
Output frequency ratio (%)
100
50
Output frequency (Hz)
Target
frequency
(100%)
99.6
93.8
87.5
10
68.4
64.6
02
35
Time
25
Acceleration time before reaching the
output frequency set value (100%)
Curve ratio 2 during
acceleration (A151)
Curve ratio 1 during
acceleration (A150)
Output frequency (Hz)
Target
frequency
(100%)
65
35.4
31.6
12.5
6.25
0.39
10
Time
50
75
Acceleration time before reaching the
Curve ratio 1 during
deceleration (A152)
Curve ratio 2 during
deceleration (A153)
Time(s)
4-2 Function Mode
02
10
Time
25
50
75
output frequency set value (100%)
4-40