Danfoss FC 100 Series Operating Instructions Manual page 79

Vlt hvac drive frequency converters
Hide thumbs Also See for FC 100 Series:
Table of Contents

Advertisement

How to Programme the Frequ...
5-40 Function Relay
Array [8]
(Relay 1 [0], Relay 2 [1]
Option MCB 105: Relay 7 [6], Relay 8 [7] and Relay 9 [8]).
Select options to define the function of the relays.
The selection of each mechanical relay is realised in an array
parameter.
Option:
[196]
Fire Mode
[197]
Fire Mode was Act.
[198]
Drive Bypass
[211]
Cascade Pump 1
[212]
Cascade Pump 2
[213]
Cascade Pump 3
6-01 Live Zero Timeout Function
Option:
Function:
Select the time-out function. The function set in
par. 6-01 Live Zero Timeout Function will be
activated if the input signal on terminal 53 or 54
is below 50% of the value in par. 6-10 Terminal 53
Low Voltage, par. 6-12 Terminal 53 Low Current,
par. 6-20 Terminal 54 Low Voltage or
par. 6-22 Terminal 54 Low Current for a time
period defined in par. 6-00 Live Zero Timeout
Time. If several time-outs occur simultaneously,
the frequency converter prioritises the time-out
functions as follows:
1.
Par. 6-01 Live Zero Timeout Function
2.
Par. 8-04 Control Timeout Function
The output frequency of the frequency converter
can be:
[1] frozen at the present value
[2] overruled to stop
[3] overruled to jog speed
[4] overruled to max. speed
[5] overruled to stop with subsequent
trip
[0]
Off
*
[1]
Freeze
output
[2]
Stop
[3]
Jogging
[4]
Max.
speed
[5]
Stop and
trip
®
VLT
HVAC Drive Operating Instructions
Function:
6-02 Fire Mode Live Zero Timeout Function
Option:
[0]
[1]
[2]
[3]
[4]
6-10 Terminal 53 Low Voltage
Range:
0.07 V
6-11 Terminal 53 High Voltage
Range:
10.00 V
®
MG.11.AD.02 - VLT
is a registered Danfoss trademark
Function:
The function set in par. 6-01 Live Zero Timeout
Function will be activated if the input signal
on analogue inputs is below 50% of the value
defined in parameter group 6-1* to 6-6*
"Terminal xx Low Current" or "Terminal xx
Low Voltage" for a time period defined in
par. 6-00 Live Zero Timeout Time.
Off
*
Freeze output
Stop
Jogging
Max. speed
Function:
[Application
Enter the low voltage value. This analog
*
dependant]
input scaling value should correspond to
the low reference/feedback value set in
par. 6-14 Terminal 53 Low Ref./Feedb.
Value.
Function:
[Application
Enter the high voltage value. This
*
dependant]
analog input scaling value should
correspond to the high reference/
feedback value set in par. 6-15 Terminal
53 High Ref./Feedb. Value.
7