3-16 Reference 2 Source
Option:
Function:
Select the reference input to be used
for the second reference signal.
par. 3-15 Reference 1 Source,
par. 3-16 Reference 2 Source and
par. 3-17 Reference 3 Source define up
to three different reference signals.
The sum of these reference signals
defines the actual reference.
This parameter cannot be adjusted
while the motor is running.
[0]
No function
[1]
Analog input 53
[2]
Analog input 54
[7]
Pulse input 29
[8]
Pulse input 33
[20]
Digital pot.meter
*
[21]
Analog input X30/11
[22]
Analog input X30/12
[23]
Analog Input X42/1
[24]
Analog Input X42/3
[25]
Analog Input X42/5
[29]
Analog Input X48/2
[30]
Ext. Closed Loop 1
[31]
Ext. Closed Loop 2
[32]
Ext. Closed Loop 3
3-19 Jog Speed [RPM]
Range:
Function:
Application
[Application
Enter a value for the jog speed n
dependent
dependant]
which is a fixed output speed. The
*
frequency converter runs at this
speed when the jog function is activa-
ted. The maximum limit is defined in
par. .
See also par. 3-80 Jog Ramp Time.
3-41 Ramp 1 Ramp Up Time
Range:
Function:
Application
[Applica-
Enter the ramp-up time, i.e. the
dependent
tion
acceleration time from 0 RPM to
*
dependant]
par. 1-25 Motor Nominal Speed. Choose
a ramp-up time such that the output
current does not exceed the current
limit in par. 4-18 Current Limit during
ramping. See ramp-down time in
par. 3-42 Ramp 1 Ramp Down Time.
t
×
n
acc
norm
par
.3 − 41 =
ref rpm
®
VLT
HVAC Drive Operating Instructions
,
JOG
par
.1 − 25
s
®
MG.11.AD.02 - VLT
is a registered Danfoss trademark
3-42 Ramp 1 Ramp Down Time
Range:
Function:
Application
[Applica-
Enter the ramp-down time, i.e. the
depend-
tion
deceleration time from par. 1-25 Motor
ent
dependant]
Nominal Speed to 0 RPM. Choose a
*
ramp-down time such that no over-
voltage arises in the inverter due to
regenerative operation of the motor,
and such that the generated current
does not exceed the current limit set in
par. 4-18 Current Limit. See ramp-up
time in par. 3-41 Ramp 1 Ramp Up
Time.
t
n
×
dec
norm
par
.3 − 42 =
ref rpm
4-10 Motor Speed Direction
Option:
Function:
Selects the motor speed direction required.
Use this parameter to prevent unwanted
reversing.
[0]
Clockwise
Only operation in clockwise direction will be
allowed.
[2]
Both directions Operation in both clockwise and anti-
*
clockwise direction will be allowed.
NOTE
The setting in par. 4-10 Motor Speed Direction has impact
on the Flying Start in par. 1-73 Flying Start.
4-11 Motor Speed Low Limit [RPM]
Range:
Function:
Application
[Application
Enter the minimum limit for motor
dependent
dependant]
speed. The Motor Speed Low Limit
*
can be set to correspond to the
manufacturer's recommended
minimum motor speed. The Motor
Speed Low Limit must not exceed
the setting in par. 4-13 Motor Speed
High Limit [RPM].
4-12 Motor Speed Low Limit [Hz]
Range:
Function:
Application
[Application
Enter the minimum limit for motor
dependent
dependant]
speed. The Motor Speed Low Limit
*
can be set to correspond to the
minimum output frequency of the
motor shaft. The Speed Low Limit
must not exceed the setting in
par. 4-14 Motor Speed High Limit [Hz].
par
.1 − 25
s
75
7
7