Danfoss FC 100 Series Operating Instructions Manual page 143

Vlt hvac drive frequency converters
Hide thumbs Also See for FC 100 Series:
Table of Contents

Advertisement

Specifications
Surroundings:
Enclosure type A
Enclosure type B1/B2
Enclosure type B3/B4
Enclosure type C1/C2
Enclosure type C3/C4
Enclosure type D1/D2/E1
Enclosure type D3/D4/E2
Enclosure type F1/F3
Enclosure type F2/F4
Enclosure kit available ≤ enclosure type D
Vibration test enclosure A, B, C
Vibration test enclosure D, E, F
Relative humidity
Aggressive environment (IEC 60068-2-43) H
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature (at 60 AVM switching mode)
- with derating
- with full output power of typical EFF2 motors (up to 90% output current)
- at full continuous FC output current
1)
For more information on derating see the Design Guide, section on Special Conditions.
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance
Temperature during storage/transport
Maximum altitude above sea level without derating
Maximum altitude above sea level with derating
Derating for high altitude, see section on special conditions
EMC standards, Emission
EMC standards, Immunity
See section on special conditions!
Control card performance:
Scan interval
Control card, USB serial communication:
USB standard
USB plug
CAUTION!
Connection to PC is carried out via a standard host/
device USB cable.
The USB connection is galvanically isolated from the
supply voltage (PELV) and other high-voltage terminals.
The USB connection is not galvanically isolated from
protection earth. Use only isolated laptop/PC as connec-
tion to the USB connector on frequency converter or an
isolated USB cable/converter.
®
VLT
HVAC Drive Operating Instructions
5% - 95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
S test
2
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
®
MG.11.AD.02 - VLT
is a registered Danfoss trademark
IP 20/Chassis, IP 21kit/Type 1, IP55/Type12, IP 66/Type12
IP 21/Type 1, IP55/Type12, IP 66/12
IP 21/Type 1, IP55/Type 12, IP66/12
IP21/NEMA 1/IP 4
EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EN 61800-3, EN 61000-6-1/2,
IP20/Chassis
IP20/Chassis
IP21/Type 1, IP54/Type12
IP00/Chassis
IP21, 54/Type1, 12
IP21, 54/Type1, 12
on top of enclosure
X
1.0 g
0.7 g
class Kd
1)
max. 55° C
max. 50 ° C
1)
max. 45 ° C
1)
0 °C
- 10 °C
-25 - +65/70 °C
1000 m
3000 m
: 5 ms
1.1 (Full speed)
USB type B "device" plug
143
9
9