Danfoss FC 100 Series Operating Instructions Manual page 46

Vlt hvac drive frequency converters
Hide thumbs Also See for FC 100 Series:
Table of Contents

Advertisement

Electrical Installation
Unsuccessful AMA
1.
The frequency converter enters into alarm mode. A
description of the alarm can be found in the Trouble-
shooting section.
2.
"Report Value" in the [Alarm Log] shows the last
measuring sequence carried out by the AMA, before
the frequency converter entered alarm mode. This
4
4
number along with the description of the alarm will
assist troubleshooting. If contacting Danfoss Service,
make sure to mention number and alarm descrip-
tion.
Par. 3-02 Minimum Reference
Par. 3-03 Maximum Reference
Par. 4-11 Motor Speed Low Limit [RPM] or par. 4-12 Motor Speed Low Limit [Hz]
Par. 4-13 Motor Speed High Limit [RPM] or par. 4-14 Motor Speed High Limit [Hz]
Par. 3-41 Ramp 1 Ramp Up Time Ramp-up Time 1 [s]
Par. 3-42 Ramp 1 Ramp Down Time Ramp-down Time 1 [s]
See the section How to programme the frequency converter,
Quick Menu Mode for an easy set-up of these parameters.
46
®
VLT
HVAC Drive Operating Instructions
NOTE
Unsuccessful AMA is often caused by incorrectly entered
motor name plate data or too big difference between
the motor power size and the frequency converter
power size.
Step 4: Set speed limit and ramp time
Set up the desired limits for speed and ramp time.
®
MG.11.AD.02 - VLT
is a registered Danfoss trademark

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents