Commissioning and Applicati...
Save frequency converter settings:
1.
Connect a PC to the unit via USB com port. (NOTE:
Use a PC, which is isolated from the mains, in
conjunction with the USB port. Failure to do so may
damage equipment.)
2.
Open MCT 10 Set-up Software
3.
Choose "Read from drive"
4.
Choose "Save as"
All parameters are now stored in the PC.
5
5
Load frequency converter settings:
The MCT 10 Set-up software modules
The following modules are included in the software package:
Ordering number:
Please order the CD containing MCT 10 Set-up Software using
code number 130B1000.
MCT 10 can also be downloaded from the Danfoss Internet:
WWW.DANFOSS.COM, Business Area: Motion Controls.

5.1.5 Tips and Tricks

For the majority of HVAC applications the Quick
Menu, Quick Set-up and Function Set-up provides
the simplest and quickest access to all the typical
parameters required
Whenever possible, performing an AMA, will ensure
best shaft performance
Contrast of the display can be adjusted by pressing
[Status] and [
[Status] and [
Under [Quick Menu] and [Changes Made] all parame-
ters that have been changed from factory settings
are displayed
Press and hold [Main Menu] key for 3 seconds for
access to any parameter
For service purposes it is recommended to copy all
parameters to the LCP, see par. 0-50 LCP Copy for
further information
50
®
VLT
HVAC Drive Operating Instructions
MCT Set-up 10 Software
Setting parameters
Copy to and from frequency converters
Documentation and print out of parameter settings incl. diagrams
Ext. user interface
Preventive Maintenance Schedule
Clock settings
Timed Action Programming
Smart Logic Controller Set-up
] for darker display or by pressing
] for brighter display
MG.11.AD.02 - VLT
1.
Connect a PC to the frequency converter via USB
com port
2.
Open MCT 10 Set-up software
3.
Choose "Open"– stored files will be shown
4.
Open the appropriate file
5.
Choose "Write to drive"
All parameter settings are now transferred to the frequency
converter.
A separate manual for MCT 10 Set-up Software is available:
MG.10.Rx.yy.
5.1.6 Quick Transfer of Parameter Settings
when Using GLCP
Once the set-up of a frequency converter is complete, it is
recommended to store (backup) the parameter settings in the
GLCP or on a PC via MCT 10 Set-up Software Tool.
Stop the motor before performing any of these
operations.
Data storage in LCP:
1.
Go to par. 0-50 LCP Copy
2.
Press the [OK] key
3.
Select "All to LCP"
4.
Press the [OK] key
All parameter settings are now stored in the GLCP indicated
by the progress bar. When 100% is reached, press [OK].
The GLCP can now be connected to another frequency
converter and the parameter settings copied to this frequency
converter.
®