Calculating Heat Dissipation - Sun Microsystems Sun Fire V210 Installation Manual

Hide thumbs Also See for Sun Fire V210:
Table of Contents

Advertisement

Power Consumption
TABLE 2-13
Server Model
Configuration
Sun Fire V210
2x1064MHz CPU
4G DIMM
2xHDD
Sun Fire V240
1x1064MHz CPU
512M DIMM
1xHDD
Sun Fire V240
2x1064MHz CPU
2G DIMM
2xHDD
Sun Fire V240
2x1280MHz CPU
2G DIMM
2xHDD
Sun Fire V240
2x1280MHz CPU
4G DIMM
2xHDD
Note – Power consumption figures refer to the power drawn from the AC feed. No
correction is required for PSU efficiency.

Calculating Heat Dissipation

To calculate the heat generated by a server so that you can estimate the heat your
cooling system must dissipate, convert the figure for the system's power
requirement from watts to BTU/hr. A general formula for doing this is to multiply
the power requirement figure in watts by 3.412.
Average Power (Watts)
Instantaneous Power (VA)
232
236
137
138
220
223
233
235
247
250