[In/Out] − [I/O setting] − [I/O terminals] − [Output]
1
Press [Output mode] and press [Level output] or
[One-shot output].
2
Press [Output delay] and set the one-shot output de-
lay.
3
Press [OK].
4
Press [Output time] and set the one-shot output time.
5
Press [OK].
Item
Output mode
One-shot output
Level output (default)
Output delay
Output time
Important
When one-shot output is selected as the output mode, make the following value smaller than the trigger input
period.
• One-shot delay time + One-shot output time
FQ User's Manual
Description
After the measurement results are finalized, if the judgement output ON condition
is met, the OR signal is turned ON for the one-shot output time. It is then turned
OFF once the specified time has expired.
The judgement is output after measurement results are finalized and the ON/OFF
status of the OR signal is held until it is changed for the next measurement result.
When one-shot output mode is selected, this parameter sets the delay from when
a measurement is completed until when the OR signal turns ON. (Setting range: 0
to 1,000 ms)
When one-shot output mode is selected, this parameter sets the time that the OR
signal is ON. (Setting range: 1 to 1,000 ms)
Controlling/Outputting in Parallel