10 Troubleshooting

10.1

Error codes

Tab.64
Error codes are displayed at three different levels
Code
Type

Warning

A00.00
(1)
H00.00
Blocking
(1)
E00.00
Lock out
(1)
(1) The first letter indicates the type of error.
Fig.87
HMI T-control
22/02/2018 11:20
Home Screen
........ .......
i
..... ... ....... .... .. ..... ....... .... ..... .......
Error Code: A.00.00
20/02/2018 16:51
.......... ......... .... ............ ........... ... ..... ....
1
...... ..... ......... ... ....... .......
.......... .........
... .........
2
Tab.65
Warning codes
Code
Display text
A.00.00
TFlow Open
A.00.01
TFlow Closed
A.01.21
Dhw Temp GradLevel3
A.02.06
Water Press Warning
7734324 - v.03 - 29092020
The boiler is fitted with an electronic regulation and control unit. The heart
of the control is a e-Smart microprocessor, which controls and also
protects the boiler. In the event of an error, a corresponding code is
displayed.
Description
The boiler continues to operate but the cause of the warning must be investigated. A
warning can change into a blocking or lock-out.
The boiler starts up again automatically when the cause of the blocking has been recti­
fied. A blocking can become a lock-out.
The boiler starts up again only when the cause of the lock-out has been rectified and
reset manually.
The meaning of the code can be found in the various error code tables.
Important
The error code is needed to find the cause of the error quickly and
correctly and for any support from Remeha.
10.1.1

Display of error codes

When an error occurs in the installation, the control panel shows:
1
The display will show a corresponding code and message.
2
The status LED of the control panel will show:
Continuous green = Normal operation
Flashing green = Warning
Continuous red = Blocking
Flashing red = Lock out
1. Press and hold the
The boiler starts up again only when the cause of the error has
been rectified.
2. If the error code reappears, correct the problem by following the
AD-3001379-01
instructions in the error code tables.
The error code remains visible until the problem is solved.
3. Note the error code when the problem cannot be solved.
10.1.2
Warning
Description
Flow temperature sensor is either
removed or measures a temperature
below range
Flow temperature sensor is either
shorted or measures a temperature
above range
Maximum Dhw Temperature Gradi­
ent Level3 Exceeded
Water Pressure Warning active
button to reset the boiler.
Solution
-
-
Temperature warning:
Check the flow.
Water pressure warning:
Water pressure too low; check the water pres­
sure
10 Troubleshooting
69