Finalising Work; Disposal And Recycling; Troubleshooting; Error Codes - REMEHA Quinta Ace 30 Service Manual

High-efficiency wall-hung gas boiler
Hide thumbs Also See for Quinta Ace 30:
Table of Contents

Advertisement

7.6

Finalising work

7.7

Disposal and recycling

Fig.59
MW-3000179-03
8

Troubleshooting

8.1

Error codes

Tab.51
Error codes are displayed at three different levels
Code
Type
A .00.00
Warning
(1)
H .00.00
Blocking
(1)
E .00.00
Lock out
(1)
(1) The first letter indicates the type of error.
(2) For some blocking errors, this checking interval is ten minutes. In those cases, it may seem that the controls do not start automatically.
Wait ten minutes before resetting.
7703943 - v.06 - 13122021
1. Fit all removed parts in the reverse order, but do not close the casing
yet.
Caution
During inspection and maintenance operations, always replace all
gaskets on the parts removed.
2. Fill the siphon with water.
3. Put the siphon back in place.
4. Carefully open all system and supply valves which were closed to
carry out the maintenance.
5. Fill the central heating system with water if necessary.
6. Vent the central heating system.
7. Top up with more water if necessary.
8. Check the tightness of the gas and water connections.
9. Put the boiler back into operation.
10. Carry out an auto-detect when a control board has been replaced or
removed from the boiler.
11. Set the boiler to full load and carry out a gas leak detection and a
thorough visual check.
12. Set the boiler to normal operation.
13. Close the casing.
Important
Removal and disposal of the boiler must be carried out by a
qualified person in accordance with local and national regulations.
To remove the boiler, proceed as follows:
1. Cut the power supply to the boiler.
2. Shut off the gas supply.
3. Shut off the water supply.
4. Drain the system.
5. Remove the siphon.
6. Remove the air supply/flue gas outlet pipes.
7. Disconnect all pipes on the boiler.
8. Remove the boiler.
The Quinta Ace is fitted with an electronic regulation and control unit. The
heart of the control is a e-Smart microprocessor, which controls and also
protects. In the event of an error, a corresponding code is displayed.
Description
The controls continue to operate, but the cause of the warning must be investigated. A
warning can change into a blocking or lock-out.
The controls will stop normal operation, and will check with set intervals if the cause of
the blocking still exists.
Normal operation will resume when the cause of the blocking
(2)
has been rectified. A blocking can become a lock-out.
The controls will stop normal operation. The cause of the lock-out must be rectified and
the controls must be reset manually.
The meaning of the code can be found in the various error code tables.