10.4 Maintenance of the air/flue gas drain connection flues

The connection pipes must be checked at least once a year.
- Check the seals.
- Check the condensates evacuation pump in the boiler and on the
pipe if used.

10.5 Temperature sensor

The resistance values at the various temperatures are indicated in
the tables on the next page.
If a faulty sensor is detected, it is possible to check the resistance at
the various temperatures using a meauring device with a
corresponing measurement range (e.g. a multimeter). In order to
obviate incorrect measurements, the sensor must be disconnected
from the connector bar in the boiler distribution panel.
Resistance of the NTC 12 sensor kOhm
(boiler water, boiler return water, flue gases)
Temperature °C
Resistance ohm Temperature °C Resistance ohm
10
22800
20
14770
30
9800
40
6650
50
4610
52
60
3250
70
2340
80
1710
90
1270
Gas 110 Eco 115 / 65
- Replace the leakproof seals and sections of pipe if these no longer
offer a perfect guarantee of leak tightness after being dismantled
during a maintenance operation (only for the visible part of the
flue).
26/01/2009 - 300014883-001-F