Parameters And Menus - Omron E5CK User Manual

Digital controller
Hide thumbs Also See for E5CK:
Table of Contents

Advertisement

CHAPTER 1 INTRODUCTION

1.3 Parameters and Menus

J Parameter types
F Protect mode
F Manual mode
F Level 0 mode
F Level 1 mode
F Level 2 mode
F Setup mode
F Expansion mode
1--6
E5CK parameters are distributed between the following nine modes.
Protect mode
Manual mode
Level 0 mode
Level 1 mode
Level 2 mode
Setup mode
Expansion mode
Option mode
Calibration mode
The settings of parameters in each of seven modes (excluding the protect
mode and manual mode) can be checked and modified by selection on the
menu display.
This mode is used to limit use of the menu and
tion is for preventing unwanted modification of parameters and switching
between the auto and manual operation.
In this mode, the controller can be switched manual operation. The
manipulated variable can be manipulated manually only in this mode.
Set the controller to this mode during normal operation. In this mode, you
may change the set point during operation, and stop and start operation.
You can also monitor (not change) the process value, ramp SP and manip-
ulated variable.
This is the main mode for adjusting control. In this mode, you can execute
AT (auto-tuning), and set alarm values, the control period and PID param-
eters.
This is the auxiliary mode for adjusting control. In this mode, you can set
the parameters for limiting the manipulated variable and set point, switch
between the remote and local modes, and set the loop break alarm (LBA),
alarm hysteresis and the digital filter value of inputs.
This is the mode for setting the basic specifications. In this mode, you can
set parameters that must be checked or set before operation such as the
input type, scaling, output assignments and direct/reverse operation.
This is the mode for setting expanded functions. In this mode, you can set
ST (self-tuning), SP setting limiter, selection of advanced PID or ON/OFF
control, specification of the standby sequence resetting method, initializa-
tion of parameters, time for automatic return to the monitoring display.
keys. The protect func-
A/M

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents