CHAPTER 5 PARAMETERS

Setup Mode
Input type
Match the setting (software) of this parameter with the setting (hardware) of the
input type jumper connector.
Set the input types to be connected to terminal Nos. 6 to 8 by the input type codes in
Function
the table below.
Set the code according to the following table. Default is "2: K1 thermocouple".
Set value
Comment
F Related article
3.2 Setting Input Specifications (page 3-3)
F Related parameters
See
When input type is set to temperature input:
"_C/_F selection" (setup mode)
When input type is set to voltage input or current input:
"Scaling upper limit" "Scaling lower limit" "Decimal point" (setup mode)
5--22
0
JPt
-199.9 to 650.0 (_C)
1
Pt
-199.9 to 650.0 (_C)
2
K1
-200 to 1300 (_C)
3
K2
0.0 to 500.0 (_C)
4
J1
-100 to 850 (_C)
5
J2
0.0 to 400.0 (_C)
6
T
-199.9 to 400.0 (_C)
7
E
0 to 600 (_C)
8
L1
-100 to 850 (_C)
9
L2
0.0 to 400.0 (_C)
10
U
-199.9 to 400.0 (_C)
11
N
-200 to 1300 (_C)
12
R
0 to 1700 (_C)
13
S
0 to 1700 (_C)
14
B
100 to 1800 (_C)
15
W
0 to 2300 (_C)
16
PLII
0 to 1300 (_C)
17
4 to 20mA
18
0 to 20mA
19
1 to 5V
20
0 to 5V
21
0 to 10V
Input Type
/-199.9 to 999.9 (_F)
Platinum resis
Platinum resis-
tance thermometer
/-199.9 to 999.9 (_F)
/-300 to 2300 (_F)
/0.0 to 900.0 (_F)
/-100 to 1500 (_F)
/0.0 to 750.0 (_F)
/-199.9 to 700.0 (_F)
/0 to 1100 (_F)
/-100 to 1500 (_F)
/0.0 to 750.0 (_F)
Thermocouple
Thermocouple
/-199.9 to 700.0 (_F)
/-300 to 2300 (_F)
/0 to 3000 (_F)
/0 to 3000 (_F)
/300 to 3200 (_F)
/0 to 4100 (_F)
/0 to 2300 (_F)
Current input
Current input
Voltage input
Voltage input
Jumper Position
TC⋅PT
TC PT
TC⋅PT
TC⋅PT
I
I
V
V

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents