Control Output - Omron E5CK User Manual

Digital controller
Hide thumbs Also See for E5CK:
Table of Contents

Advertisement

F Input
5
10
11 12
4
9
3
8
2
7
13 14
1
6
F Control output
5
10
11 12
4
9
3
8
2
7
13 14
1
6
Connect the input to terminal Nos. 6 to 8 as follows according to the
input type.
8
-
7
6
+
Thermocouple Platinum resistance
thermometer
TC PT
Match the inputs with the internal jumper settings for each input type.
For thermocouple or platinum resistance thermometer inputs, set the
inputs to a common position (TC/PT) as the temperature input. For
details on jumper connector positions, see page 2-2.
Terminal Nos. 11 and 12 are for control output 1 (OUT1). The five out-
put types and internal equalizing circuits are available according to out-
put unit:
+
+v
11
11
12
12
GND
-
Relay
NPN
E53-R4R4
E53-Q4R4
E53-Q4Q4
Terminal Nos. 9 and 10 are for control output 2 (OUT2). The three out-
put types and internal equalizing circuits are available according to out-
put unit:
10
9
Relay
E53-R4R4 /E53-V44R4
E53-Q4R4 /E53-C4R4
E53-Q4HR4/E53-C4DR4
The following table shows the specifications for each output type.
Output Type
Relay
250VAC, 3 A
Voltage (NPN)
12VDC, 20 mA (with short-circuit protection)
Voltage (PNP)
12VDC, 20 mA (with short-circuit protection)
0 to 10V
0 to 10VDC, Permissible load impedance:
1 k min., Resolution: Approx. 2600
4 to 20mA
4 to 20 mA, Permissible load impedance:
500
0 to 20mA
0 to 20 mA, Permissible load impedance:
500
8
8
-
7
7
mA
V
6
6
+
Voltage input
V
+
+v
11
L
L
V
GND
12
-
PNP
0 to 10V
E53-Q4HR4
E53-V44R4
E53-Q4HQ4H
+
+v
+v
10
L
GND
9
GND
-
NPN
E53-Q4Q4
E53-Q4HQ4H
Specifications
max., Resolution: Approx. 2600
max., Resolution: Approx. 2600
2.3 Wiring Terminals
8
-
7
6
+
Current input
I
+
+
11
11
L
L
mA
12
12
-
-
4 to 20mA/0 to 20mA
E53-C4R4
E53-C4DR4
+
10
L
9
-
PNP
2--7