CHAPTER 5 PARAMETERS
Expansion Mode
AT calculated gain
Sets the gain when adjusting the PID parameters by auto-tuning.
To give priority to response, decrease the set value of this parameter. To give priority
to stability, increase the set value of this parameter.
Function
Comment
F Related parameters
"AT Execute/Cancel" (level 1 mode)
"PID / ON/OFF" (expansion mode)
See

Standby sequence reset method

Selects the conditions for enabling reset after the standby sequence of the alarm has
been canceled.
Condition A:
Function
Control started (including power ON), and set point, alarm value or input shift value
changed, and when set points 1 and 2 are switched.
Condition B:
Power ON
0: Condition A / 1: Condition B
Comment
F Related parameters
"Alarm 1 type" "Alarm 2 type" "Alarm 3 type" (setup mode)
See
5--30
Unit
Setting Range
0.1 to 10.0
None
Setting Range
Conditions of Use
The control must be advanced PID con-
trol, and ST must be set to OFF.
Default
1.0
Default
0