CHAPTER 5 PARAMETERS
Option Mode
Communication stop bit
Communication data length
Communication parity
These parameters set the communications conditions. Make sure that the stop bit,
data length, parity and baud rate of the host computer and the E5CK controller are
matching. These parameters are valid when the power is turned ON again or when
Function
level 0 to 2 modes are switched.
When connecting two or more E5CK controllers to the host computer, set unit Nos.
that will not conflict with the unit Nos. of other controllers.
"Communication stop bit" parameter
Comment
"Communication data length" parameter
"Communication parity" parameter
"Communication baud rate" parameter
"Communication unit No." parameter
F Related article
Capter 6 Using the Communications Function (page 6-1)
F Related parameter
See
"Remote/Local" (level 2 mode)
F Option unit
RS-232C unit (E53-CK01), RS-485 unit (E53-CK03)
Model
5--34
Unit
Setting Range
1, 2
Bits
Unit
Setting Range
7, 8
Bits
Setting
: None/
:Even/
Setting Range
1.2, 2.4, 4.8, 9.6, 19.2
Unit
Setting Range
0 to 99
None
Conditions of Use
The communications function must be in
use.
Default
2
Default
7
Default
:Odd
Unit
Default
kbps
9.6
Default
0
Communication baud rate
Communication unit No.