Parameters And Menus - Omron E5EK - MANUAL 2 User Manual

Digital controller compobus/d (devicenet) type
Hide thumbs Also See for E5EK - MANUAL 2:
Table of Contents

Advertisement

CHAPTER 1 INTRODUCTION

1.3 Parameters and Menus

+ Parameter types
' Protect mode
' Manual mode
' Level 0 mode
' Level 1 mode
' Level 2 mode
' Setup mode
' Expansion mode
Differences from
General-purpose
Models
1–6
E5EK DRT parameters are distributed between the following nine modes.
Protect mode
Manual mode
Level 0 mode
Level 1 mode
Level 2 mode
Setup mode
Expansion mode
Option mode
Calibration mode
The settings of parameters in each of seven modes (excluding the protect
mode and manual mode) can be checked and modified by selection on the
menu display.
This mode is used to limit use of the keys. The protect function is for pre
venting unwanted modification of parameters and switching between the
auto and manual operation.
In this mode, the controller can be switched manual operation. The
manipulated variable can be manipulated manually only in this mode.
Set the controller to this mode during normal operation. In this mode, you
may change the set point during operation, and stop and start operation.
You can also monitor (not change) the process value, ramp SP and manip
ulated variable.
This is the main mode for adjusting control. In this mode, you can execute
AT (auto tuning), and set alarm values, the control period, PID parame
ters and heater burnout alarm (HBA) conditions.
This is the auxiliary mode for adjusting control. In this mode, you can set
the parameters for limiting the manipulated variable, switch between the
remote and local modes, switch between the SP modes, and set the loop
break alarm (LBA), alarm hysteresis and the digital filter value of inputs.
This is the mode for setting the basic specifications. In this mode, you can
set parameters that must be checked or set before operation such as the
input type, scaling, output assignments and direct/reverse operation.
This is the mode for setting expanded functions. In this mode, you can set,
SP setting limiter, selection of 2 PID control or ON/OFF control, specifi
cation of the standby sequence resetting method, time for automatic
return to the monitoring display.
New function
Functions not supported
CompoBus/D
Serial communications
(DeviceNet)
Position-proportional control
Event input
Multi-SP
Transfer output
Self-tuning (ST)