Checking Indication Accuracy - Omron E5CK User Manual

Digital controller
Hide thumbs Also See for E5CK:
Table of Contents

Advertisement

CHAPTER 4 APPLIED OPERATION
J Checking indica-
tion accuracy
F Thermocouple
AC100-240V
(AC/DC24V )
F Platinum resis-
tance thermome-
ter
F Current or volt-
age input
4--20
After calibrating input, make sure that you check indication accuracy to
make sure that the E5CK controller has been correctly calibrated.
Operate the E5CK controller in the PV/SP monitor (level 0 mode) mode.
Check the indication accuracy at the upper and lower limits and mid-
point.
Preparation
The following figure shows the required device connection. Make sure
that the E5CK controller and cold junction compensator are connected
by a compensating conductor for the input type that is to be used during
actual operation.
5
11 12
SOURCE
4
3
2
13 14
1
Operation
Make sure that the cold junction compensator is at 0_C, and set STV out-
put to the voltage equivalent to the starting power of the check value.
Preparation
The following figure shows the required device connection.
AC100-240V
(AC/DC24V )
SOURCE
Operation
Set the 6-dial to the resistance equivalent to the check value.
Preparation
The following figure shows the required device connection.
AC100-240V
(AC/DC24V )
SOURCE
Operation
Set the STV to the current or voltage value equivalent to the check value.
10
9
Cold junction
compensator
8
7
6
Compensating
conductor
5
10
11 12
4
9
3
8
2
7
13 14
1
6
5
10
11 12
4
9
3
8
2
7
13 14
1
6
STV
6-dial
STV