Specifications - Omron E5CK User Manual

Digital controller
Hide thumbs Also See for E5CK:
Table of Contents

Advertisement

APPENDIX

SPECIFICATIONS

J Ratings
Supply Voltage
Power Consumption
Operating Voltage
Range
Input
Input Impedance
Control Output
Auxiliary Output
Control Method
Setting Method
Indication Method
Other Functions
Ambient Temperature
Ambient Humidity
*1 Thermocouple W is W/Re5-26 (tungsten rhenium 5, tungsten rhenium 26).
*2 The following table shows the setting ranges and indication ranges for each of the inputs.
A--2
AC100--240V type
AC100--240V
~
, 50/60 Hz
15VA
85% to 110% of rated supply voltage
Thermocouple : K, J, T, E, L, U, N, R, S, B, W, PLII
Platinum resistance thermometer : JPt100, Pt100
Current input : 4 to 20mA, 0 to 20mA
Voltage input : 1 to 5V, 0 to 5V, 1 to 10V
Voltage input : 1 MΩ min.
Current input : 150 Ω
According to output unit (see "Output Unit Ratings and Characteristics")
SPST-NO, 1A at 250 VAC (resistive load)
Advanced PID or ON/OFF control
Digital setting using front panel keys
7-segment digital display and LEDs
According to option unit (see "Option Unit Ratings and Characteristics")
Operating : -10°C to 55°C (with no icing)/3-year warranty period: -10°C to 50°C
Storage : -25°C to 65°C (with no icing)
35% to 85% RH
Input
Setting Range
JPt100
--199.9 to 650.0(_C)
Pt100
--199.9 to 650.0(_C)
K1
--200 to 1300(_C)
K2
0.0 to 500.0(_C)
J1
--100 to 850(_C)
J2
0.0 to 400.0(_C)
T
--199.9 to 400.0(_C)
E
0 to 600(_C)
L1
--100 to 850(_C)
L2
0.0 to 400.0(_C)
U
--199.9 to 400.0(_C)
N
--200 to 1300(_C)
R
0 to 1700(_C)
S
0 to 1700(_C)
B
100 to 1800(_C)
W
0 to 2300(_C)
PLII
0 to 1300(_C)
4 to 20mA
One of following ranges depending on results of
scaling
0 to 20mA
--1999 to 9999
1 to 5V
--199.9 to 999.9
0 to 5V
--19.99 to 99.99
--1.999 to 9.999
0 to 10V
AC/DC24V type
AC/DC24
6VA, 3.5W
/--199.9 to 999.9(_F)
--199.9 to 735.0(_C)
/--199.9 to 999.9(_F)
--199.9 to 735.0(_C)
/--300 to 2300(_F)
--350 to 1450(_C)
/0.0 to 900.0(_F)
--50.0 to 550.0(_C)
/--100 to 1500(_F)
--195 to 945(_C)
/0.0 to 750.0(_F)
--40.0 to 440.0(_C)
/--199.9 to 700.0(_F)
--199.9 to 460.0(_C)
/0 to 1100(_F)
--60 to 660(_C)
/--100 to 1500(_F)
--195 to 945(_C)
/0.0 to 750.0(_F)
--40.0 to 440.0(_C)
/--199.9 to 700.0(_F)
--199.9 to 460.0(_C)
/--300 to 2300(_F)
--350 to 1450(_C)
/0 to 3000(_F)
--170 to 1870(_C)
/0 to 3000(_F)
--170 to 1870(_C)
/300 to 3200(_F)
--70 to 1970(_C)
/0 to 4100(_F)
--230 to 2530(_C)
/0 to 2300(_F)
--130 to 1430(_C)
-10 to 110% of setting range. Note, however that
max. value is -1999 to 9999
, 50/60Hz
*1, *2
Indication Range
/--199.9 to 999.9(_F)
/--199.9 to 999.9(_F)
/--560 to 2560(_F)
/--90.0 to 990.0(_F)
/--260 to 1660(_F)
/--75.0 to 825.0(_F)
/--199.9 to 790.0(_F)
/--110 to 1210(_F)
/--260 to 1660(_F)
/--75.0 to 825.0(_F)
/--199.9 to 790.0(_F)
/--560 to 2560(_F)
/--300 to 3300(_F)
/--300 to 3300(_F)
/10 to 3490(_F)
/--410 to 4510(_F)
/--230 to 2530(_F)

Hide quick links:

Advertisement

Table of Contents
loading