11-1-5 Megger Test

Before performing a megger test on external circuits, be sure to disconnect all the terminals of the
inverter and not to apply the test voltage to the inverter. Use a 500 VDC megger for a megger test.
For a megger test on the inverter main circuit, short-circuit the terminals R/L1, S/L2, T/L3, U/T1, V/T2,
W/T3, RB, +1, P/+2, and N/− with wires, as shown below.
Because the insulation resistance rating of the single inverter unit is 5 MΩ or higher, it is normal if the
resistance is 5 MΩ or higher.
• For the inverter, do not perform a megger test on the control circuit. Perform it only on the main cir-
cuit.
• Use a tester (in a high resistance range) for a power-on test on the control circuit. Do not use a meg-
ger or buzzer.
500-VDC megger
Do not connect the
power supply wires.

11-1-6 Withstand Voltage Test

Do not conduct a withstand voltage test on any part of the inverter.
Doing this test is dangerous because it may cause damage to or deterioration of the parts inside the
inverter.

11-1-7 Inverter/Converter Unit Test

Use the following procedure to check conditions of the inverter and converter units by using a tester.
Preparation
1
Disconnect the externally connected power supply wires (R/L1, S/L2, T/L3), the motor
connection wires (U/T1, V/T2, W/T3), and the regenerative braking resistance (P/+2, RB).
2
Prepare a tester. Use the 1 Ω resistance measurement range.
Multi-function Compact Inverter 3G3MX2-V1 User's Manual (I585-E1)
RB
+1
R/L1
S/L2
T/L3
U/T1
Power supply
11 Maintenance and Inspection
P/+2
N/-
Ground
terminal
V/T2
W/T3
Do not connect to the
IM
motor.
Motor