7 Other Functions
Set-frequency Only Signal (C021, C022, C026 = 06: FA3, 25: FA5)
The inverter outputs the frequency arrival signal only when the inverter reaches the frequency set in the
Arrival Frequency During Acceleration 1/2 (C042/C045) or Arrival Frequency During Deceleration 1/2
(C043/C046).
Output frequency
FA3/FA5 output
fon: 1% of maximum frequency
foff: 2% of maximum frequency

7-8-10 RUN Time/Power ON Time Over (RNT/ONT)

If the total RUN time or power ON time of the inverter exceeds the RUN Time/Power ON Time Detection
Level (b034), the inverter will output the RUN time over (RNT) or Power ON time over (ONT) signal.
Parameter
No.
RUN Time/Power ON
b034
Time Detection Level
Multi-function Output
P1/P2 Selection,
C021, C022
Multi-function Relay Out-
C026
put (MA, MB) Function
Selection
Related functions
RUN Time Over (C021, C022, C026 = 11: RNT)
Allocate the Multi-function Output P1/P2 Selection (C021/C022) or Multi-function Relay Output (MA,
MB) Function Selection (C026) to 11 (RNT: RUN time over).
Set the RUN Time/Power ON Time Detection Level (b034).
Power ON Time Over (C021, C022, C026 = 12: ONT)
Allocate the Multi-function Output P1/P2 Selection (C021/C022) or Multi-function Relay Output (MA,
MB) Function Selection (C026) to 12 (ONT: Power ON time over).
Set the RUN Time/Power ON Time Detection Level (b034).
7 - 82
f
off
C042/C045
f
on
Function name
0.
Function is disabled
1. to 9999.
Set in increments of 10 hours (10 to 99,990 h)
1000 to 6553 (10000 to 65530)
Set in increments of 100 (10) hours
(100,000 to 655,300 h)
11:
12:
d016, d017
Data
RNT (RUN time over)
ONT (Power ON time over)
Multi-function Compact Inverter 3G3MX2-V1 User's Manual (I585-E1)
f
on
C043/C046
f
off
Default
Unit
data
0.
10 hex