5-10 Multi-function Output Settings

5-10-1 Multi-function Output Selection

• You can allocate the functions shown in the following table to the multi-function output P1 and P2
terminals, and the multi-function relay output (MA, MB) terminals.
• This section describes seven types of primary functions. For other functions, refer to 7-2
Multi-function Input/Output Functions on page 7-18.
• Set the functions in the Multi-function Output P1/P2 Selection (C021/C022) and the Multi-function
Relay Output (MA, MB) Function Selection (C026) to use them.
• The multi-function output P1 and P2 terminals are for open collector output and the multi-function
relay output (MA, MB) terminals are for relay output.
• The default data of Multi-function Relay Output (MA, MB) Function Selection (C026) is 05 (AL: Alarm
signal). Therefore, the Multi-function Relay Output (MA, MB) Operation Selection (C036) is set to 01
(NC: NC contact) by default.
This manual describes each function with the Multi-function Output Operation Selection set to 00
(NO: NO contact). Note that the operations of the Multi-function Relay Output (MA, MB) are reversed.
Parameter
No.
Multi-function
Output P1/P2
Selection
(C021/C022)
Multi-function
Relay Output
(MA, MB)
Function
Selection
(C026)

5-10-2 Multi-function Output Operation Selection

• Set the multi-function output P1/P2 terminals and the multi-function relay output (MA, MB) terminals
to either NO (NO contact) or NC (NC contact) individually.
• This manual describes each function with the Multi-function Output Operation Selection set to 00
(NO: NO contact). Note that the signal operations are reversed when you set them to 01 (NC: NC
contact).
Parameter
No.
C031
C032
C036
Multi-function Compact Inverter 3G3MX2-V1 User's Manual (I585-E1)
Data
Function name
00
RUN:
Signal during RUN
01
FA1:
Constant speed arrival signal Constant speed arrival signal
05
AL:
Alarm signal
21
ZS:
0 Hz detection signal
50
IRDY:
Operation ready
51
FWR:
Forward run signal
52
RVR:
Reverse run signal
Function name
Multi-function Output P1
Operation Selection
Multi-function Output P2
Operation Selection
Multi-function Relay Output
(MA, MB) Operation
Selection
Reference item
Signal during RUN
Alarm signal
0 Hz detection signal
Operation ready signal
Forward run signal
Reverse run signal
Data
00:
NO (NO contact)
01:
NC (NC contact)
00:
NO contact between MA and MC,
NC contact between MB and MC
01:
NC contact between MA and MC,
NO contact between MB and MC
5 Basic Settings
Page
P. 5-56
P. 5-57
P. 5-57
P. 5-58
P. 5-59
P. 5-59
P. 5-59
Default
Unit
data
00
01
5 - 55