Omron MX2 Series User Manual page 429

Mx2 series type v1 multi-function compact inverter
Hide thumbs Also See for MX2 Series:
Table of Contents

Advertisement

Response
No.
1
Slave address
2
Function code
3
Coil start address (MSB)
4
Coil start address (LSB)
5
Number of coils (MSB)
6
Number of coils (LSB)
7
CRC-16 (MSB)
8
CRC-16 (LSB)
*1. During a broadcast, no response will be sent back.
*2. Note that the coil start address is 0006, which is 1 less than the coil number 0007: Coil start address = Coil
number - 1.
*3. Since written data occupies both MSB and LSB as a set, make the data to have an even number of bytes by
adding one byte of padding data, even if you actually need to change an odd number of bytes.
A multi-function input terminal is recognized as ON when either the terminal block input or the commu-
nications setting turns ON.
Also note that the Multi-function Input Monitor (d005) monitors the terminal block input only.
If the Write to Multiple Coils function is not executed normally, refer to 8-5-9 Exception Response on
page 8-20.
(Example) When the status of coils from coil number 0001 to 000D hex is written, the order of data is
as shown below. Data 1 is the initial byte data to send.
Data 1
0008 hex
Data 2
Multi-function Compact Inverter 3G3MX2-V1 User's Manual (I585-E1)
Example
Field name
[hex]
*1
*2
*2
bit 7
bit 6
bit 5
0007 hex
0006 hex
8 Communications Functions
01
0F
00
06
00
07
F4
08
bit 4
bit 3
0005 hex
0004 hex
000D hex
000C hex
bit 2
bit 1
bit 0
0003 hex
0002 hex
0001 hex
000B hex
000A hex
0009 hex
8
8 - 17