Using Multi-step Speed Reference
Allocate one of the Multi-function Input S1 to S7 Selection (C001 to C007) to 02 to 05 or 32 to 38
(Multi-step speed) and turn ON that terminal. This enables the inverter to perform multi-step speed
operation, independent of Frequency Reference Selection (A001/A201) settings.
The frequency depends on the value set in the Multi-step Speed Reference 1 to 15 (A021 to A035).
However, at the 0th speed where multi-step input signals are all OFF, the frequency depends on the
1st/2nd Frequency Reference Selection (A001/A002) setting.
Parameter No.
A001/A201
A019
C001 to C007
A020
A220
A021 to A035
*1. Only the frequency reference at the 0th speed depends on the 1st/2nd Frequency Reference Selection
(A001/A002) setting.
*2. To enable the switching to the 2nd control, allocate one of the Multi-function Input Terminal S1 to S7 Selection
(C001 to C007) to 08 (SET) and turn ON that terminal.
Multi-function Compact Inverter 3G3MX2-V1 User's Manual (I585-E1)
V
Communications etc.
Set value in A001/A201
Function name
1st/2nd Frequency
02:
Reference Selection
00:
Multi-step Speed
Selection
01:
02 to 05:
Multi-function Input
S1 to S7 Selection
32 to 38:
0.00
1st Multi-step Speed
Starting Frequency to 1st Maximum Fre-
*1
Reference 0
quency
0.00
2nd Multi-step
Speed Reference
Starting Frequency to 2nd Maximum Fre-
*2
0
quency
0.00
Multi-step Speed
Reference 1 to 15
Starting Frequency to Maximum Frequency
Data
*1
Digital Operator (F001)
Binary (16-step selection with 4 termi-
nals)
Bit (8-step selection with 7 terminals)
CF1 to CF4
Binary 15-step
SF1 to SF7
Bit 7-step
5 Basic Settings
Default data
Unit
02
00
6.00
Hz
0.00
Hz
5 - 29