Torque Ladstop Function Settings - Omron MX2 Series User Manual

Mx2 series type v1 multi-function compact inverter
Hide thumbs Also See for MX2 Series:
Table of Contents

Advertisement

6 Vector Control and Applied Functions
Precautions for Correct Use
When the torque limit function is used in a low speed range, the inverter may fail to start the
motor and detect an overload. In this case, use this function in conjunction with the overload
limit selection (b021/b221/b024).
6-2-2

Torque LADSTOP Function Settings

Use this function to stop temporarily the frequency acceleration/deceleration function (LAD) when the
torque limit function is activated. This function, as well as the torque limit function, is enabled when the
1st/2nd Control Method (A044/A244) is set to 03 (Sensorless vector control).
• LAD functions to calculate the transient frequency reference value to enable the motor to reach the
reference frequency in the set acceleration/deceleration time.
• This function stops the frequency reference temporarily at the transient value calculated by LAD
when the torque limit function is activated and restarts at that frequency when the torque limit is reset.
• To stabilize the motor operation after resetting the torque limit, enable this function.
Parameter No.
b045
Related functions
Output frequency
TRQ output
(During torque limit)
6 - 14
Function name
00:
Torque LADSTOP
Selection
01:
A044, A244, b040, b041 to b044
Torque limit is activated (During torque limit)
Transient frequency calculated by LAD changes even when torque
limit function is activated (b045 = 00).
Transient frequency calculated by LAD stops changing temporarily
when torque limit function is activated (b045 = 01).
Time
Data
Disabled
Enabled
Multi-function Compact Inverter 3G3MX2-V1 User's Manual (I585-E1)
Default
Unit
data
00